Life Cycle Assessment of a compact Desiccant Evaporative Cooling system: The case study of the “Freescoo”
2016
Abstract The paper aims at exploring the performances of a compact Desiccant Evaporative Cooling system called “Freescoo” (Free Solar Cooling) in comparison to standard conventional technologies. The Freescoo – that aims at applications in the residential sector and in small office buildings and includes a photovoltaic–thermal system – is analyzed, its monitored performance discussed and reported: under cooling conditions an Energy Efficiency Ratio of 12.8 is calculated, that reaches 50.7 if also photovoltaic generation is considered. To assess the performance of the proposed system a Life Cycle Assessment study was performed to investigate the system covering all its life, from the product…